STRUCTURAL ENGINEERING COMPONENTS
Doors & pass-through cabinets
Electronic Access control, Air tight doors are part of the barrier such as shower-exits, airlocks, emergency exits.Shower out system
At least 3 showers, each of 40 litres of water, 5 minutes cycle.
Air Handling System
Graded negative pressure w.r.t atmospheric pressure is maintained. Air is exhausted to atmosphere through HEPA Filters.
It comprises of 23 AH units with 97 HEPA filters fitted in 92 filter housings (Lab-58, animal wing -25, ETP and others- 09).
ETP (Liquid Waste Sterilization Plant)
All the effluents collected from different points and sterilized by heat(121oC, 30 min) at the basement 3 mt and 5.3mt below the ground level.
Barrier autoclaves
Double door steam based barrier autoclaves for sterilization of solid wastes.Ethylene trioxide Sterilizer
Heat sensitive materials such as electronic equipments/ gadgets etc. are passed through ETO.Air lock
Formaldehyde fumigation through a 16 h program.Incinerator
All the waste generated is incinerated.Equal Opportunity for Persons with Disabilities